Miniverter
4
General
The Miniverter 230 V mains input must be protected by
a fuse or circuit breaker of 6 A for 500 VA or 10 A
for 800 VA and 13 A for 1100 VA, ‘Klippon’
type terminal blocks are used for cable termination
in the power management and bypass module, fuses and
circuit breakers should sized to accept inrush current
‘slow’ characteristic. Maintenance free
recombination monobloc batteries are supplied as optional
items and the recharge float voltage is set at 54.48
V DC (nominal 48 V DC), the minimum autonomy battery
is supplied within the bypass module.
Options
- Psophometric filtering to
meet CCITT requirements.
- RFI suppression filters.
- Interconnecting plugs and
sockets between UPS module and bypass module.
- Battery module with maintenance
free lead acid or NiCad batteries to give autonomy
up to 8 hours.
- External station battery
connection facilities with blocking diode and protection.
- CEGB approval options pack
for NGC, National Power, Powergen, Scottish Nuclear
and Nuclear Electric.
- Miniverter 2, special seismic
qualified construction with external station battery
connection for Nuclear power stations and military
applications with integral automatic bypass.
- Miniverter CCITT special
inverter available for connection to Telecoms 48 V
DC station battery.
Typical
Scheme

Dimensions

The Miniverter 4 series of rugged,
industrial class of Uninterruptible Power Supply Systems
are designed to provide high security power for process
engineering, data logging, military, instrumentation,
public utility and telecoms applications.
Miniverters are active-on-line UPS
Systems which provide galvanic separation between mains
and DC and between the critical load and the mains.
A full capacity rectifier provides continuous power
for the inverter and simultaneously charges the battery
module. This series of rack mounting UPS Systems are
of a modular construction with rectifier, inverter,
bypass and battery available as separated items. Metering,
status indication with remote signalling features and
distribution modules are available as popular options
with this product.
The inverter is a PWM - Pulse Width
Modulation type using the latest in high frequency transistor
switching technology producing a precisely regulated
AC Sine Wave output with an exceptional performance
to handle switch mode and other non-linear loads.
In the event of commercial mains failure,
the inverter draws its power from the battery module
or the station battery and will continue to supply the
critical load without any disturbance until the battery
low level is reached or when power has been restored
to the rectifier.
Where abnormal overload conditions
or over temperature conditions impact the continued
operation of the inverter the automatic bypass switch
will operate. The bypass switch module enables the critical
load to be transferred to the bypass circuit automatically,
then returns the load back to the inverter without disturbing
the critical load security. A manual maintenance bypass
is also provided.
| Rectifier |
Input Voltage, Single phase &
Neutral |
110/220/230/240 V (+/- 15%)* |
| Input Frequency |
50 (60 Hz) +/- 5% |
| Power Factor (mean value) |
0.8 |
| Battery Charging characteristic |
IU (DIN 41773) |
| Input Transformer |
Double wound isolation with galvanic separation |
| Inverter |
Input Voltage |
48 V DC nominal |
| Nominal output power cos phi 0.8 lag |
500 VA 800 VA 1100 VA |
| Nominal output power at 1.0 cos phi |
400 W 640 W 800 W |
| Crest factor of load |
2.25:1 |
| Nominal output voltage, single phase+neutral |
110/220/230/240 V * |
| Inverter |
High frequency transistor with
pulse width modulation (PWM),
over temperature protection. |
| Output transformer |
Double wound isolation with
galvanic separation |
| Output filter |
LC - circuit |
| Output waveform |
Sine-wave |
| Output voltage regulation: |
 |
| static |
+/- 1% |
| at load step with 100 % load change |
+/- 3% |
| output distortion at linear load |
<3% |
| Output frequency |
50(60) Hz |
| Output frequency regulation: |
 |
| free running, from internal oscillator |
+/- 0.1% |
| with mains synchronisation |
Up to +/-4%, normally +/-1% |
| Overload capability |
110% for 10 minutes
150% for 30 seconds
200% for 10 seconds |
| Short-circuit characteristic |
Electronic short-circuit protection |
Bypass
separate
19” rack
module |
Electronic automatic |
Load transfer to mains and
automatically back to inverter |
| Maintenance bypass |
Automatic or switch selectable
by rotary switch on front panel |
| Input and output |
By 2 switches on front panel |
*Supplied for single voltage single frequency operation
Miniverter Series RT
General
Ambient operating temperature to 40°C in relative
humidity of 97% non condensing, at 1000 m above sea
level is permitted without de-rating, conditions must
be dust and damp free, and well ventilated.
RFI suppression level is in accordance with VDE 0875N.
Psophometric filtering for CCITT is available on inverters
requested for Telecoms applications as an optional feature.
Colour
Colour is RAL 7032 with textured finish.
Enclosure
Enclosure class IP30 to IEC 529 for RTC product and
IP 20 for RT.
Options
- Alternative enclosure class to IP 54
- Custom colours
- Digital metering
- Customers requested features
Notes
- Single phase means one phase + neutral and earth
- Three phase means three phase lines + neutral and
earth
- The RTC version of this product is provided with
a full height door and inner safety screen with EMC
shield
Typical Scheme

Typical construction
and dimensions

Our Industrial Miniverter Rugged Transistor (RT) series
of rack constructionb Uninterruptible Power Supply Systems
are designed to provide a high security power source
for computer based process control, data logging, SCADA,
military, telecommunications, rail signalling and Public
Utilities applications especially Nuclear Power Stations.
This product range has an active-on-line system topology
comprising full capacity rectifier, transistor PWM inverter,
static bypass and manual maintenance bypass.
During normal mains operation, the rectifier produces
DC for charging the battery and power for the inverter
load. The inverter uses the latest in transistor PWM
switching technology and converts the DC into a precisely
regulated AC sinusoidal output waveform low in harmonic
content with excellent dynamic performance ideally suitable
for handling high crest factor non-linear loads. In
the event of input power failure, the Miniverter RT
draws power from the battery and will continue to supply
the critical load with AC power until the battery ‘low’
threshold is reached or until input power has been restored
to the rectifier.
Where abnormal overload conditions or over temperature
or current limit is reached in the inverter, the static
bypass switch will be activated to transfer the critical
load from the inverter to the bypass power source without
interruption. The static bypass features an automatic
return of the critical load from the bypass line to
the inverter also without interrupting power supply
to the load, a manual maintenance bypass is also provided
as a standard feature.
Miniverter RTC series UPS Systems and inverters are
available in a compact, integrated execution fitted
with a full height front door, safety interior screen,
EMC shield, mimic status and alarm panel and basic metering,
a full metering option is available.
Specification (2.5 kVA,
3.3 kVA, 5 kVA, 8 kVA, 10 kVA and 12 kVA)
| UPS system size |
2.5 |
3.3 |
5.0 |
8.0 |
10.0 |
12.0 |
| Rectifier |
Input Voltage |
230 Volts +/- 15% |
400 Volts +/- 15% |
400 Volts +/- 15% |
| Frequency |
50 Hz +/- 5% |
50 Hz +/- 5% |
50 Hz +/- 5% |
| Phases |
Single + neutral + earth |
3 phases + neutral + earth |
3 phases + neutral + earth |
| Inverter |
Rated Capacity
kVA/kW |
2.5/2 |
3.3/2.7 |
5.0/4 |
8.0/6.4 |
10.0/8 |
12.0/9.6 |
| Output Voltage: |
 |
 |
 |
 |
 |
 |
| - Single Phase |
230 |
230 |
230 |
230 |
230 |
230 |
| - Three Phases |
- |
- |
400 |
400 |
400 |
400 |
| Voltage Regulation: |
 |
 |
 |
 |
 |
 |
| - Normal |
+/- 1% |
+/- 1% |
+/- 1% |
+/- 1% |
+/- 1% |
+/- 1% |
| - Dynamic |
+/-3% |
+/-3% |
+/-4% |
+/-5% |
+/-8% |
+/-8% |
| Frequency |
50 Hz |
50 Hz |
50 Hz |
50 Hz |
50 Hz |
50 Hz |
| Phases: |
 |
 |
 |
 |
 |
 |
| - Single Phase |
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
| - Three Phases |
No |
No |
Yes |
Yes |
Yes |
Yes |
| Load Power Factor |
0.7 lagging to unity within kW capacity |
| Harmonic Distortion |
<3% THD linear load |
<5% THD linear load |
| Overload Capacity |
150% for 30 secs
120% for 10 mins |
150% for 30 secs
120% for 10 mins |
Audible noise at
1 metre |
<57 dBA |
<57 dBA |
<57 dBA |
<57 dBA |
<57 dBA |
<57 dBA |
Bypass
separate
19” rack
module |
Automatic synchronised static transfer
switch with separate manual bypass circuit breaker
for maintenance. A bypass isolation transformer
and voltage regulating transformer are available
as optional items. |
| Notes |
- Other voltages and frequencies available.
- Frequency stability is +/- 1% when synchronised
to mains and +/- 0.01% when free running.
|
Selection Data - Miniverter
4
UPS
Module
|
6U high x 482 wide x 470 deep (mm)
excluding handles
Weights: 500 VA 23 kg 800 VA 45 kg 1100VA 53 kg |
| Inverter
only |
5U high x 482 wide x 470 deep (mm) excluding handles
Weights: 500 VA 20 kg 800 VA 33 kg 1100 VA 39 kg |
| Bypass
BP1 |
3U high x 482 wide x 375 deep (mm) excluding handles
Weight with internal battery approx 10 min autonomy
500 VA 16 kg
800 VA 19 kg
1100 VA 24 kg |
Power
management
BM4 |
2U high x 482 wide x 375 deep (mm) no handles
Input, output, bypass and battery isolation with
mimic status feature - weight 11 kg |
Battery
Module BM1 |
3U high x 482 wide x 375 deep (mm) excluding handles
Weight with internal battery approx 10 min autonomy
500 VA 15 kg
800 VA 18 kg
1100 VA 23 kg |
Battery
Module BM2 |
6U high x 482 wide x 375 deep (mm) excluding handles
Weight 5 kg without batteries |
Selection Data - Miniverter
RT/RTC
| kVA
|
Phases |
Battery Autonomy |
Dimensions
(mm) |
Weight (Kg) |
| Input |
Output |
volts |
Minutes |
H |
W |
D |
UPS |
Battery |
| 2.5 |
1 |
1 |
48 |
15 |
1080 |
600 |
600 |
165 |
44 |
| 1 |
1 |
48 |
60 |
1400 |
600 |
600 |
165 |
95 |
| 3.5 |
1 |
1 |
72 |
15 |
1080 |
600 |
600 |
180 |
67 |
| 1 |
1 |
72 |
30 |
1400 |
600 |
600 |
195 |
104 |
| 5 |
3 |
1 |
120** |
0¤ |
1080 |
600 |
600 |
210 |
-° |
| 3 |
1* |
120 |
30 |
1400 |
600 |
600 |
240 |
110 |
| 8 |
3 |
1* |
120** |
0¤ |
1080 |
650 |
700 |
300 |
-° |
| 3 |
1 |
120** |
15 |
1600 |
650 |
700 |
380 |
132 |
| 3 |
1 |
120** |
30 |
1800 |
650 |
700 |
390 |
235 |
| 12 |
3 |
1 |
120** |
0¤ |
1400 |
700 |
750 |
390 |
-° |
| 3 |
1 |
120** |
15 |
1800 |
700 |
750 |
410 |
174 |
| 3 |
3 |
120** |
0¤ |
1400 |
700 |
750 |
395 |
-° |
| 3 |
3 |
210** |
15 |
1800 |
700 |
750 |
420 |
174 |
| * |
3 Phase available as option |
| ** |
48 V DC input inverter available for telecoms |
| ° |
No built in battery |
| ¤ |
RTC models have provision for battery
RT models have no provision for batteries |
|
|